ORDERING INFORMATION • Code number: R5-PC2[1][2] Specify a code from below for each [1] and [2]. (e.g. R5-PC2W/Q) • Specify the specification for option code /Q (e.g. /C01)
NO. OF CHANNELS 2: 2-point outputs
[1] COMMUNICATION MODE S: Single W: Dual
[2] OPTIONS blank: none /Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
GENERAL SPECIFICATIONS Connection Internal bus: Via the Installation Base (model: R5-BS) Output: Euro type connector terminal (Applicable wire size: 0.2 – 2.5 mm2 (AWG24 - 12), stripped length 7 mm) Internal power: Via the base (model: R5-BS) Isolation: Po 1 to Po 2 to internal bus or internal power RUN indicator: Bi-color (red/green) LED; Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally. Output status indicator: Red LED; turns on with the outputs ON. Pulse width adjustment: 5 msec., 10 msec., 50 msec., 100 msec., 500 msec., 1 sec., 1.5 sec., 2 sec. (Side DIP SW) Count reset: Via DIP switches on the side
OUTPUT SPECIFICATIONS Output: Photo MOSFET relay contact, 2 points Common: Each point independent Rated load: 125 V AC/DC @ 50 mA (resistive load) Maximum ON resistance: 50 Ω Maximum frequency: 100 Hz (DIP SW selectable) Totalized pulse range: 1 – 10000 (‘0’ at reset) (Max. pulse range selectable from 100 to 60000 using the R5CON PC Configurator Software. Refer to the R5CON Users Manual for detailed information.) Count at overflow: Reset and restart at ‘1.’
INSTALLATION Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R5-BS) Weight: 100 g (3.53 oz)
PERFORMANCE Data allocation: 2 Response time: ≤ 0.1 sec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (Po 1 to Po 2 to internal bus or internal power) 2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1,EN 61010-2-201 Measurement Category II (output) Pollution Degree 2 Output to internal bus or internal power – Basic insulation (300 V) RoHS Directive EN 50581
FUNCTIONS ■ Counter reset 1) Remove Network Module or its cables and interrupt communication with other devices. 2) Turn ON the Counter Reset SW (SW8) on the module. 3) Return the module to the base and turn the power supply on. 4) Red RUN LED turns on and the module starts resetting its counter. When the resetting is complete, the LED light turns to green. DO NOT remove the power while the red light is on. 5) After the green LED is confirmed, turn the power supply off. 6) Turn OFF the Counter Reset SW (SW8). 7) Return the Network module onto the base and turn the power supply on. Note: Counter Reset SW must be turned OFF after this procedure because the module does not start counting with ON state.
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)