·Some details are not shown. Please refer to specification sheets for all information.
R5-YV
Remote I/O R5 Series
DC VOLTAGE OUTPUT MODULE
MODEL: R5-YV[1][2][3]
ORDERING INFORMATION • Code number: R5-YV[1][2][3] Specify a code from below for each [1] through [3]. (e.g. R5-YV2W/Q) • Specify the specification for option code /Q (e.g. /C01)
[1] NO. OF CHANNELS 1: 1 2: 2
[2] COMMUNICATION MODE S: Single W: Dual
[3] OPTIONS blank: none /Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
GENERAL SPECIFICATIONS Connection Internal bus: Via the Installation Base (model: R5-BS) Output: Euro type connector terminal (Applicable wire size: 0.2 – 2.5 mm2 (AWG24 - 12), stripped length 7 mm) Internal power: Via the base (model: R5-BS) Isolation: Output 1 to output 2 to internal bus or internal power Output range: Selectable with the side DIP SW RUN indicator: Bi-color (red/green) LED; Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally.
OUTPUT SPECIFICATIONS ■ Narrow Span: -1 – +1 V, 0 – 1 V DC Load resistance: 10 kΩ min. ■ Wide Span: -10 – +10 V, -5 – +5 V, 0 – 10 V, 0 – 5 V, 1 – 5 V DC Load resistance: 10 kΩ min. ■ Output Range Except -10 to +10 V DC: -15 to +115 % of output range -10 to +10 V DC: Approx. -11.5 to +11.5 V DC
INSTALLATION Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R5-BS) Weight: 100 g (3.53 oz)
PERFORMANCE Output range v.s. conversion accuracy (Narrow span) -1 – +1 V DC : ±0.1 (%) 0 – 1 V DC : ±0.1 (Wide span) -10 – +10 V DC : ±0.05 -5 – +5 V DC : ±0.05 0 – 10 V DC : ±0.05 0 – 5 V DC : ±0.05 1 – 5 V DC : ±0.05 Data range: 0 – 10000 of the output range Data allocation: 1 (2 for 2-channel type) Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time: ≤ 0.2 sec. (0 – 90 %) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (output 1 to output 2 to internal bus or internal power) 2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581
FUNCTIONS Output hold function: In normal conditions, the module outputs the signal from the preferred bus A. When an error is detected, the output is switched to the data from the bus B. If both are in error, the module holds the signal and stands by until one of the communications recovers. At the startup, it outputs -15 % (or approx. -11.5 V) of the selected range until the communication is established and normal data is received.
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)